Cooling method looks like a technical detail on a datasheet. In practice it decides how much maintenance the transformer needs and whether it keeps its rated output in year eight.
What the two mean
ONAN is oil natural, air natural: the oil circulates by convection and the tank dissipates heat to still air. There are no moving parts. ONAF adds fans and oil pumps: the same tank and windings deliver roughly 25–30 % more power, but only while the fans run.
Why ONAF is often the wrong default
ONAF lets a manufacturer quote a smaller, cheaper unit for the same kVA, which is why it appears in many low bids. The cost moves to the site: fans fail, dust blocks radiators, and the auxiliary supply has to be available whenever the load is high. In a remote substation without maintenance staff, an ONAF unit that loses its fans is an ONAN unit with a lower rating than the load requires.
When ONAF is the right answer
- The load is genuinely cyclic and the peak is short — fans run for a few hours a day.
- Site maintenance is organised, with spares and a schedule.
- Footprint or transport weight is the binding constraint, so a physically smaller unit is worth the complexity.
A practical specification rule
Ask for the ONAF rating and the ONAN rating, and design the network around the ONAN figure. Then ONAF becomes a bonus for peak periods rather than a dependency. A unit specified this way never runs beyond its natural-cooling capability if the fans stop.
If the enquiry does not state a preference, say so and let the manufacturer justify the choice against your site conditions — including who will maintain the fans.