Home / Products / 110 kV Power Transformers

Products

110 kV power transformers with on-load tap changers, 6.3 – 63 MVA

Two- and three-winding oil-immersed power transformers for 110 kV substations, with on-load tap changing as standard, cooling to ONAN / ONAF / OFAF, and routine test records issued with every unit — third-party type testing arranged to your specification.

110 kV Power Transformers, 6.3 – 63 MVA

Technical specification

Typical values. Confirm the exact figures for your project in the enquiry — impedance, loss limits and insulation levels are usually dictated by your tender.

6.3 – 63 MVA110 kV

Rated power6.3 MVA – 63 MVA
Voltage class110 kV (equipment level 123 kV)
WindingTwo-winding or three-winding
CoolingONAN / ONAF / OFAF, to load profile
Tap changerOn-load (OLTC), ±8 × 1.25 % typical
Vector groupYNd11 standard; YNyn0d11 and others on request
Impedance10.5 % typical, to customer specification
CoreCRGO silicon steel, 45° step-lap mitred joints
Insulation levelLI 480 kV / AC 200 kV (110 kV class)
LossesTo IEC 60076-20 or your tender’s evaluation formula
StandardsIEC 60076, GB 1094; IEEE C57 on request
TestingRoutine tests in our own works on every unit; third-party type test at an accredited laboratory on request
Standard lead time60 days from approved drawing — the build is slower at this insulation level, and a third-party type test, if specified, is booked inside this figure
Multi-unit and project ordersScheduled in the quotation, against the delivery date you give us

The unit itself

Photographed in our own works before packing — no stock images, no renders standing in for a product we do not build.

110 kV Power Transformers — view 1
110 kV Power Transformers — view 2
110 kV Power Transformers — view 3

Design points that matter on site

Each of these comes from problems customers brought to us after buying elsewhere.

On-load tap changing as standard

OLTC fitted as the default configuration, so voltage correction happens under load rather than requiring an outage.

Type testing arranged to your requirement

Routine tests — ratio, resistance, impedance, losses, applied and induced voltage — are carried out in our own works on every unit, and the records travel with the transformer. For 110 kV units a third-party type test at an accredited laboratory can be reserved as part of the order; the report is issued directly to you. Tell us at enquiry stage whether your consultant requires it witnessed, because it changes the delivery slot.

Transport and site conditions planned up front

Above 40 MVA, transport weight and route clearances usually decide the design. We confirm shipping constraints before the drawing is frozen.

Loss evaluation taken seriously

Core and winding geometry optimised to whichever loss capitalisation formula your tender applies, with calculated figures supplied in the bid.

Typical applications

  • 110 kV substations
  • Utility transmission and distribution
  • Industrial main substations
  • Renewable energy grid connection

Delivered to projects across the Middle East and Africa. Reference lists are available on request.

Next step

Send your parameters for this product

Rated power, voltage ratio, cooling method and quantity is enough to start. We reply with price, lead time and an outline drawing.